System Sensor PDRP-1002 User Manual

Page 35

Advertising
background image

FM-Approved Releasing Devices

Appendix B: Device Compatibility

The PDRP-1002 PN 51135:A 03/11/99

35

Table 7 UL Listed, Compatible Two-Wire Smoke Detectors for Notifier Control Panels

Number of
Detectors Per Zone

Model

Det.
ID

Detector Type

Base Model

Base
ID

Standby
Current
(uA)

PDRP-1002/
PDRP-1002E

System Sensor 1400

A

Ionization

n/a

n/a

100

20

System Sensor 1451

A

Ionization

B401B / B406B

A

120

15 / 1

System Sensor 1851DH

A

Ionization

DH1851DC

A

120

15

System Sensor 2400

A

Photoelectric

n/a

n/a

120

15

System Sensor 2400AIT

A

Photo / Isolated
Thermal / Horn

n/a n/a

120

1

System Sensor 2400AT

A

Photo / Thermal / Horn

n/a

n/a

120

1

System Sensor 2400TH

A

Photo / Thermal

n/a

n/a

120

15

System Sensor 2451

A

Photoelectric

B401B / B406B

A

120

15 / 1

System Sensor 2451TH

A

Photo / Thermal

B401B / B406B

A

120

15 / 1

System Sensor 2851DH

A

Photoelectric

DH2851DC

A

120

15

System Sensor 1451DH

A

Ionization

DH-400

A

120

15

System Sensor 2451

A

Photoelectric

DH-400

A

120

15

System Sensor 2300T

A

Photo / Thermal

n/a

n/a

120

15

System Sensor 1800

A

Ionization

n/a

n/a

100

n/a

System Sensor 1851B

A

Ionization

B101B

A

120

n/a

System Sensor 1851B

A

Ionization

B107B

A

120

n/a

System Sensor 2800

A

Photoelectric

n/a

n/a

120

n/a

System Sensor 2800TH

A

Photo / Thermal

n/a

n/a

120

n/a

System Sensor 2851B

A

Photoelectric

B101B

A

120

n/a

System Sensor 2851B

A

Photoelectric

B107B

A

120

n/a

System Sensor 2851BTH

A

Photo / Thermal

B101B

A

120

n/a

System Sensor 2851BTH

A

Photo / Thermal

B107B

A

120

n/a

System Sensor 1151

A

Ionnization

B401 / B110LP /
B116LP

A

120

15 / 15 / 1

System Sensor 2151

A

Photoelectric

B401 / B110LP /
B116LP

A

120

15 / 15 / 1

Advertising