3 Installation Procedure

Zones

16

The PDRP-1002 PN 51135:A 03/11/99

Initiating Device Circuits

Zones

Wire all alarm initiating devices sequentially for proper supervision. Initiating devices
include: heat, photoelectric, and ionization type detectors; and waterflow alarm
devices. Refer to the Compatibility Chart in Appendix B.

Note:

Observe polarity when connecting polarized devices.

All circuits are supervised and power limited.

Leave Dummy Load (provided) on all unused circuits.

Figure 4 Example of an Alarm Initiating Device

B+ A+ A- B- B+ A+ A- B- B+ A+ A- B- B+ A+ A- B-

TB 4

+

+

+

+

+

+

_

_

_

_

_

_

1

2

3

4

5

6

7

8

9

10

11

12

13

14

15

16

A

ID

EX.

c

d

r

IN #1

IN #2

IN #3

IN #4

Manual

Pull Station

Heat

Detector

Two-wire

Smoke

Detector

Class B (Style B)

Initiating Device Circuit

4.7K, 1/2-Watt (part # 71252 UL listed)

Class A (Style D)

Initiating Device

Circuit

Abort Switch

4.7K, 1/2-Watt

(part # 71252

UL listed)

Manual Release

4.7K, 1/2-Watt

(part # 71252

UL listed)