NFPA 72 Signaling Systems for Central Station Service

Appendix C: NFPA Standard-Specific Requirements

The PDRP-1002 PN 51135:A 03/11/99

37

NFPA 72 Signaling Systems for Central Station Service

(Protected Premises Unit) and Remote Station Fire Alarm System (Protected Premises Unit)

NOTI•FIRE 911AC DACT* - for connection to a Central Station Receiver or Protected
Premises Receiving Unit. This unit must be installed as illustrated below. For
additional information on the 911AC, refer to document 74-06200-005.

All connections between the FACP and 911AC must be in conduit, less than 20 ft
(609.6cm) in length in the same room. If the NOTI•FIRE 911AC is not mounted in the
PDRP-1002/PDRP-1002E backbox all connections must be in conduit, less than 20 ft.
(609.6 cm) in length in the same room.

*This application using the NOTI•FIRE 911AC is not FM approved.

Note: For 911AC

The Maximum standby load shall be 125 mA.

The Standby by Battery Requirement: 24VDC, 7Amp-Hour-Max.

The PDRP-1002/PDRP-1002E is not suitable for transmission of a supervisory signal to the DACT.

Figure 13 NFPA 72 Signaling Systems for Central Station Service

1
2

4

6
7
8
9

10
11
12

3

5

1
2

5
6
7
8
9

10

12
13
14
15
16
17

3
4

11

1 2VAC , 20VA, 60Hz or +2 4VD C

1 2VAC , 20VA, 60Hz or -2 4VD C

(R efer to m an ua l)

B AT TE RY -

B AT TE RY +

INI T IAT IN G A1 -

INI T IAT IN G A2 -

INI T IAT IN G B1 +

INI T IAT IN G B2 +

S U PE RV IS OR Y H I

S U PE RV IS OR Y LO

T ROU B L E R EL AY N C

T ROU B L E R EL AY C O M

T ROU B L E R EL AY N O

A LA R M R ELAY N C

A LA R M R ELAY C OM

A LA R M R ELAY N O

D i g it a l Ala rm C o mm u n ic a t or Tra n sm it t e r L i st e d for C e ntr al S ta t i o n o r R e m o te S ta t i on S e rv ic e.

S lid e C ov er B ack to A cces s Pro gr am m in g Ja c k a n d R el ay s

P ri ma r y R J 31 X

Te l co Ja c k

A lte rn a te R J3 1 X

Te l co Ja c k

- 1 2 V D C Se a le d
R e c h a rg e ab le

+ B a tt e ry

PS1270

12Volt

7AH Battery

+

-

NOTE on STD DACT:
Place jumper over pins 2 and 3,
marked DACT, when employing a
DACT. This directs the control panel
to transmit all trouble conditions
except AC LOSS.

STD DACT

To Central Station

Alarm

JP-1

Motherboard 911AC

Alarm

normally open
contacts

TB3-1

6 and 7

TB3-3

8 and 9

Trouble

normally open
contacts

TB3-4

10

TB3-6

11

Note: The PDRP-1002/
PDRP-1002E is not
suitable for transmission
of a supervisory signal to
the DACT

RP

911

AC.

C

D