3. Project database,

4. Job-specific application programming code,

5. All other documentation.

PART 2 - PRODUCTS

2.01 MANUFACTURERS

A. Regardless of the manufacturer, the specific products and design chosen shall meet the

requirements of this specification.

B. Use the manufacturers listed below or in the description of the devices:

1. Control Wiring

a. TVSS surge protectors

1. Leviton 51010WM or Kelle HSP-121BT IRU or pre-approved equal.

b. Infinet Communication Wiring

1. Windy City, Belden or equal: 24 gauge stranded, single twisted pair, shielded,
low capacitance (less than 12.5 pico-farads/ft), 78% velicity of propagation.

2. Control Valves

a. Hot Water and Chilled Water; Globe Style; Terminal Units, AHU Coils, Baseboard

Radiation.

1. ½” - ¾” size; Honeywell VP-525A or C series (2-way, NO, VP-526A (3-way,

VP-527A (2-way, NO, and VP-531A or C series (2-way, NO, or preapproved
equal Siemens Powermite 599 Series (electric) or Siemens Powermite 599

(pneumatic).

Honeywell VP-522A and B Series (sequencing applications).

2. For 1” and 1 ¼” sizes only; Powers VP-658 (2-way, NO or NC), VP-658WM

(3-way) and VP-591 are also acceptable.

4.

b. Hot Water and Chilled Water; Globe Style; Control of Differential Pressure

(Bypass) in Hydronic Systems.

1. 1" - 8" Size; Siemens 200 Series Electric Actuators or pre-approved equal.

c. Condenser Water; Butterfly Style; Condenser Water Temperature Control (Cooling

Tower Bypass).