JANUARY

2008

UCCS

STANDARDS

15950-19

5. Individual damper sections shall not have a single dimension (length or height) greater

than 48". Provide a minimum of one damper actuator per section.

6. Modulating dampers shall provide a linear flow characteristic where possible. Size

the dampers to achieve this characteristic and and consider approved blade dampers fot
this application.

7. Dampers shall have exposed linkages.

B. Control dampers shall be parallel or opposed-blade type as below or as scheduled on

drawings.

1. Outdoor and/or return air mixing dampers and face-and-bypass (F&BP) dampers shall

be combination parallel/opposed-blade, approximately 57% OB, arranged to direct
airstreams towards each other.

2. Other modulating dampers shall be opposed-blade type.

3. Two-position shutoff dampers may be parallel or opposed-blade type with blade and

side seals.

2.05 LOCAL CONTROL PANELS

A. All outdoor control cabinets shall be fully-enclosed, NEMA-1 construction, with hinged

door, key-lock latch, baked-enamel finish, removable sub-panels, UL-listed, wall-mounted

or free-standing as indicated on plans.

B. Panels shall house the microprocessor, modem, communication interface, all controllers

(except those required at VAV boxes), relays, indicators, clocks, switches, pilot lights,

override timers, etc., to allow quick access for adjustment and troubleshooting.

C. Manual switches and indicating devices shall be flush-mounted on panel face.

D. Internal components shall be securely mounted on removable sub-panels. Each component

shall be individually labeled with function and device identification, as shown on
control/interlock shop drawings.

E. Interconnections between internal and face-mounted devices pre-wired with color-coded

stranded conductors neatly installed in plastic troughs and/or tie-wrapped. Terminals for

field connections shall be UL-listed for 600-volt service, individually identified per

control/interlock drawings, with adequate clearance for field wiring. Control terminations

for field connection shall be individually identified per control drawings.

F. Provide on/off power switch with over-current protection and a 1-1/2” main air gauge for

control pressure sources to each local panel. Provide a 120-volt duplex outlet inside each

control panel that houses a DDC controller (except VAV controllers) if there is not an out-