JANUARY

2008

UCCS

STANDARDS

15950-17

2.02 AIR TUBING AND CONTROL WIRING

A. Air tubing shall be either copper (ACR) in exposed areas, or Type FR polyethylene (within

conduit). Soft copper is acceptable in concealed areas.

B. Cables shall be shielded when so recommended by manufacturer. Conductor size shall be in

accordance with manufacturer's recommendations subject to specified minimum size. See
Part 3 for allowable types.

C. All insulated wire to be copper conductors, UL labeled for 90C minimum service.

D. Raceway for both wiring and pneumatic tubing shall be per Division 16.

E. The Contractor shall provide and install:

1. TVSS surge protectors for incoming 120 VAC power to all controllers. Surge

protectors furnished shall be UL 1449 listed.

2. Transient voltage protection for all twisted pair and coaxial data communication lines

between controllers. Provide all required repeaters to assure signal integrity.


2.03 CONTROL VALVES

A. Shall be two-way or three-way type for two-position or modulating service as scheduled,

shown on drawings, or as specified in Sequence of Operation.

B. Closeoff (differential) Pressure Rating: Valve actuator and trim shall be furnished to

provide the following minimum closeoff pressure ratings:

1. Water Valves:

a. Two-way - 150% of total system (pump) head.

b. Three-way - 300% of pressure differential between ports A and B at design flow

or 100% of total system (pump) head.

2. Steam Valves: 150% of operating (inlet) pressure.

C. Water Valves: [Note to Consultant: The consultant shall provide a schedule for the

Controls Contractor listing the available pressure drop to be used for valve sizing for

each control valve in the project, unless it is a reverse-return system. It is not

acceptable to list a single pressure drop to be used for all valves. For a piping system in

which modulated two-way valves are used, for example, the valves nearest the pump

will have a larger available pressure drop than those farther away from the pump.]

1. Body and trim style and materials shall be per manufacturer's recommendations for

design conditions and service shown, with equal percentage ports for modulating
service, except where stated otherwise.