STANDARDS

15950-2

SECTION 15950

CONTROLS

[Note to Consultant: These standards incorporate the suggested wording for contract
specifications. The consultant is responsible for making sure that the specifications

are edited to meet the scope and intent of the project. Items which specifically

require editing are highlighted in bold and enclosed in brackets.]

PART 1 - GENERAL

1.01 RELATED WORK SPECIFIED ELSEWHERE

General Requirements Divisions 0 and 1

Mechanical Division 15

Testing, Balancing, and Adjusting Section 15990

Electrical Division 16

[Note to Consultant: Include Commissioning here if used.]

A. The General Conditions of the Contract, Supplementary Conditions, and General Require-

ments bound herewith are a part of these Specifications and shall be used in conjunction

with this Division as a part of the Contract Documents. Consult them for further

instructions pertaining to this work. Contractors shall be responsible for, and be governed

by, all requirements thereunder.

B. Electrical wiring in connection with the automatic temperature control system, where

shown on the Division 16 drawings, shall be performed by the Electrical Contractor. All
other wiring required for proper operation of the automatic temperature system shall be

performed by this Contractor.

C. The automatic temperature control valves, separable wells for immersion sensors, and taps

for flow and pressure instruments shall be provided by the Controls Contractor for

installation by the Mechanical Contractor under the Controls Contractor's supervision.

D. All automatic temperature control dampers shall be provided by the Controls Contractor for

installation by the Mechanical Contractor under the Control Contractor's supervision, unless

they are components of packaged equipment.

[Note to Consultant: Cross-reference the control-damper specification in 15950 in the

section in which products utilizing control dampers are specified. The dampers used

in packaged equipment shall conform to the damper specification in this section.]

E. Adjustments of manual balancing devices, as required to obtain design air and/or water