2. Line-voltage thermostats shall be UL-listed, SPDT, SPST, or DPST with contact rat-

ing suitable for application, maximum 2F differential.

3. Low-voltage thermostats shall be single or multi-stage heating and/or cooling type as

required by application.

a. Combination heating/cooling thermostats shall have independent adjustments for

heating and cooling setpoints and shall not allow setpoint cross-over.

b. Provide individual heat or cooling anticipator for each control stage. Anticipator

shall be matched to connected load, or shall be adjustable.

c. Microprocessor-based programmable type thermostats, when used, shall not lose

time or program on power failures of 12 hours or less.

4. Provide locking enclosures/guards for all thermostats located in public areas such as

lobbies, corridors, gyms, cafeterias, classrooms, auditoriums, pools, theaters, stores,
warehouses, garages, etc.

B. Room Humidistat:

1. All wall-mounted room humidistats shall have locking covers with concealed setpoint

adjustment, minimum range 30-60% RH. Omit humidity indicator when possible.

2. Provide metal guards with security screws for all humidstats located in public areas

such as lobbies, corridors, gyms, cafeterias, classrooms, auditoriums, pools, theaters,
stores, warehouses, garages, etc.

C. Duct, Immersion, and Outdoor Thermostats:

1. Provide single or multistage type with contact arrangement and rating suitable for

application. Line voltage units shall be UL-listed.

2. Sensing element shall be liquid-filled, remote-bulb type or bi-metal type as required.

a. Remote bulb type shall have sufficient capillary lengths to allow mounting of

thermostat at convenient location for adjustment.

b. Provide separable wells for immersion applications.

c. Provide sun shields for outdoor sensing bulbs.

d. Provide ambient temperature compensation where thermostat body is subjected

to outdoor ambient temperature variations.

3. Individual stage differential -2F maximum (fixed). Provide adjustable differential

type when thermostat is used for capacity control of DX refrigeration or to cycle fans.

D. Duct Humidistats:

1. Shall be line or low-voltage type utilizing non-organic sensing element. Contact