Watlow Series 935B User’s Manual

Setting Inputs and Outputs

Key Input/Output Set-up Information

• All initial input and output set-up occurs in the Configuration Menu.

• Indication of °C or °F units of measure occurs only in the

[`C_F]

prompt.

Sensor input type minimum and maximum range (see p. 53) is further

defined with Range Low

[``rL]

and Range High

[``rh]

to set the

working span of set points and remote set point scaling.

• Output 1 and Output 2 configure the prime functions of the Series 935B,

they are the “golden” prompts.

• Output 1 must be heat or cool to use Output 2 as a timer.

• Front Panel Lock

[`FPL]

requires a customer-supplied external switch

wired on Terminals 3 and 4. Switch open = unlocked; closed = locked.
Select this feature with

[`rts]

=

[`fpl]

.

• Remote Timer Start requires a customer-supplied switch on Terminals 3

and 4. Switch closed = start. Select this feature with

[`rts]

=

[tmr]

.

• Output 2 sets timer interval in hours:minutes

[thM]

or minutes:seconds

[tMS]

.

• Display Default

[dISP]

lets you choose the primary (last 2 characters) and

secondary (first 2 characters) default displays. Press

ß

to toggle to the

secondary display for 15 seconds.

[``Ac]

= Normal Display: Actual Temperature

Secondary: None

[AcSP]

= Normal Display: Set Point Temperature

Secondary: Actual Temperature

[Acti]

= Normal Display: Time Remaining

Secondary: Actual Temperature

[TiAc]

= Normal Display: Actual Temperature

Secondary: Time Remaining

[tiSP]

= Normal Display: Set Point Temperature

Secondary: Time Remaining

Configuration Menu

[``In]

Input Type

[`C_F]

Celsius/Fahrenheit

[``rL]

Input Range Low

[``rh]

Input Range High

[`Ot1]

Output 1 Function

[`Ot2]

Output 2 Function

[`rts]

Remote Timer Start

[dISP]

Display Default

[ALty]

Alarm Type

[AhYs]

Alarm Hysteresis

[`LAt]

Alarm Latch

[`SIL]

Alarm Silencing

[FAIL]

Failure Mode

[tIM]

Timer Function

[Strt]

Start Timer

[`rdY]

Timer Ready Band

[``St]

Signal Time

[SLOC]

Set Point Lockout

[`tAG]

Lockout Tag