Configuration menu, Setting inputs & outputs, Choose sensor type. see p. 23 for sensor ranges – Watlow Series 935B User Manual

Page 23: Select lowest displayable set point. ranges, p. 23, In] [`c_f] [``rl] [``rh] [`rts] [`ot2] [disp

Advertising
background image

Watlow Series 935B User’s Manual 23

Table 8 - Setting Inputs and Outputs

NOTE: Access to Configuration Menu varies with lockout function. See p. 21.

Input Type - Choose sensor type.

[```J]

[```H]

[```t]

[```n]

[```E]

[```S]

[`rtd]

[`r†d]

J t/c

K t/c

T t/c

N t/c

E t/c

S t/c

1.0° RTD

0.1° RTD

Celsius/Fahrenheit - Choose displayed unit of measure.

[``°F]

[``°C]

°F

°C

Input Range Low - Select lowest displayable Set Point, dependent on

[``In]

.

[``In]

[``rh]

Select a value (lowest displayable set point) between
Input Type Range Low and Input Range High.

Input Range High - Select highest displayable Set Point, dependent on

[``In]

.

[``rL]

[``In]

Select a value (highest displayable set point) between
Input Type Range High and Input Range Low.

Output 1 Function - Choose Output 1 type.

[hEAt]

[COOL]

[ALM]

[nonE]

Heat

Cool

Alarm

None

Output 2 Function - Choose Output 2 type (dependent on Output 1 choice).

[hEAt]

[COOL]

[ALM]

[thM]

[tMS]

[nonE]

Heat

Cool

Alarm

Timer

Timer

None

Hr./Min.

Min./Sec

Remote Timer Start - Choose Off, Front Panel Lock, or Timer (Hrs:Min).

[`off]

[`fpl]

[tmr]

Off

Front Panel Timer
Lock

Display Default - Choose the primary (last 2 characters) and secondary (first 2 characters) default displays. Press

ß

to toggle to the secondary display for 15 seconds.

[``Ac]

[[AcSP]] [Acti]

[tiAc]

[tiSP]

No secondary

Actual temp.

Actual temp.

Time remaining Time remaining

Actual temp.

Set pnt temp.

Time remaining Actual temp.

Set point temperature

Input Range Information
J t/c:

32

to

1382°F

or

0

to

750°C

K t/c:

-328

to

2282°F

or

-200

to

1250°C

T t/c:

-328

to

662°F

or

-200

to

350°C

N t/c:

32

to

2282°F

or

0

to

1250°C

S t/c:

32

to

2642°F

or

0

to

1450°C

E t/c:

-328

to

1470°F

or

-200

to

799°C

1° RTD (DIN):

-328

to

1292°F

or

-200

to

700°C

0.1° RTD:

-99.9

to

999.9°F

or

-99.9

to

700.0°C

Valid Output Functions
First select Output 1:

Then select Output 2:

Heat

None, Cool, Alarm, Timer

Cool

None, Heat, Alarm, Timer

Alarm

None, Heat, Cool

None

Heat, Cool, Alarm

• The function of Output 1 determines the options available for

Output 2.

• First select the function of Output 1. Refer to the table (right),

then select the function of Output 2.

[``In]

[`C_F]

[``rL]

[``rh]

[`rts]

[`Ot2]

[dISP]

Configuration Menu

[`Ot1]