[`tA9] = [P```];

or if

[Pb`c]

≠ 0

3°F or 2°C

[```1] [`999]

[```1] [`555]

[``)1] [99(0]

[``)1] [55%0]

Select a value in whole
degrees (1°F to 999°F or
1°C to 555°C) or in
tenths of degrees (0.1°F
to 999.0°F or 0.1°C to
555.0°C).

[hYSc]

Hysteresis Cool

[`tA9] = [P```];

or if

[`Ot1]

≠ [cool]

and/or

[`Ot2]

≠ [cool]

25°F or 17°C

[```0] [`999]

[```0] [`555]

[``)0] [99(0]

[``)0] [55%0]

Select a value in whole
degrees (0°F to 999°F or
0°C to 555°C) or in
tenths of degrees (0.0°F
to 999.0°F or 0.0°C to
555.0°C).

[Pb`c]

Proportional Band Cool

[`tA9] = [P```];

or if

[`Ot1] = [cool] and

[`Ot2]

≠ [hEAt];

or if

[`Ot1] = [hEAt] and

[`Ot2]

≠ [cool]

0°F or 0°C

[```0] [`999]

[```0] [`555]

[``)0] [99(0]

[``)0] [55%0]

Select a value in whole
degrees (0°F to 999°F or
0°C to 555°C) or in
tenths of degrees (0.0°F
to 999.0°F or 0.0°C to
555.0°C).

[``db]

Dead Band

[`tA9] = [P```];

or if

[Pb`h] = 0

1.0 second

[``)1] [`6)0]

[``%0] [`6)0]

Select a value between
0.1 and 60.0 seconds
(Solid-State Relay or
Switched DC) or 5.0 and
60.0 seconds
(Electromechanical
Relay).

[Ct`h]

Cycle Time Heat

Watlow Series 935A User’s Manual 5 3