Auto-tuning

Manual Tuning

For optimum performance, tune the Series 935B to your thermal system.
The settings here are for a broad spectrum of applications;
your system may have different requirements.

Tune heating outputs at a set point above ambient temperature.
Tune cooling outputs at a set point below ambient temp.

1. Apply power to the 935B and enter a set point.

In the Operations Menu,

[`Aut]

must =

[``no]

.

Begin with these Configuration Menu settings:

[Pb`h

=

[```1]

,

[``1t]

=

[`000]

,

[``dE]

=

[`000]

,

[Ct`h]

=

[``50]

,

[`CAL]

=

[```0]

.

2. Proportional Band Adjustment: Gradually increase

[Pb`h]

until the upper

display temp. stabilizes at a constant value.

3. Integral Adjustment: Gradually decrease

[``It]

from 30.00 until the dis-

play temperature begins to oscillate or “hunt.” Then slowly increase

[``It]

until the upper display stabilizes again near set point.

4. Cycle Time Adjustment: Set

[Ct`h]

as required. Faster cycle times some-

times achieve the best system control. However, if a mechanical contactor
or solenoid is switching power to the load, a longer cycle time will mini-
mize wear on relays.

5. Derivative Adjustment: Increase

[``dE]

to 0.10 minute. Then raise set

point by 20° to 30°F, or 11° to 17°C. Observe approach to set point. If load
temperature overshoots, increase

[``dE]

by 0.50 minute. Raise set point

by 20 to 30°F, or 11 to 17°C and watch approach again. Repeat until sys-
tem rises to new set point appropriately.

6. Calibration Offset Adjustment: Enter the

[`CAL]

offset value you want.

Calibration offset adds or subtracts degrees from the value of the input
signal.

Auto-tuning the Series 935B

Auto-tune automatically sets PID parameters for your system.

1. Press

.

and

,

for three seconds.

2. You'll see

[`Aut

]

.

3. Press and hold

ß

, then select

[`YES]

with

.

or

,

.

[tune]

will

flash to indicate auto-tuning. Display reverts to normal after auto-tuning.

4.

[`Aut]

=

[``no]

stops auto-tuning.

NOTE:

[`Aut]

is

not visible at
factory default.

ç

CAUTION:
Successful Series
935B auto-tuning
requires 3 oscillations
thru the 90% set point
in 85 min. or less. If the
system cannot perform
the oscillations in that
time, the control will
revert to the previous
PID values.

NOTE:

Manual tuning is a slow
procedure, taking from
minutes to hours to
obtain optimum value.

Figure 7 - Auto-tuning the Series 935B

Temperature

Time

90%

Set Point

Operations Menu

[`Aut]

Auto-tune

[`ALO]

Alarm Range Low

[`Ah1]

Alarm Range High

[tMr]

Countdown Timer

[IdLE]

Idle

[`L-r]

Local / Remote

[`Pid]

PID

[CnFg]

Configuration

Auto-tuning occurs at 90%
of set point in less than or
equal to 85 minutes