Watlow Series 935B User’s Manual

Errors and Troubleshooting

Key Error Information

Set up an input failure operation mode at the

[FAIL]

prompt in the

[CnFG]

menu; choose bumpless

transfer

[bPLS]

for smooth output action transition to percent power control, or select a percent power

output value.

[FAIL}

[bPLS]

Bumpless Transfer

when errors occur, the control output will continue at a percent output learned while stable. Default =

[bPLS]

.

[-100] [`100]

Percent Power

(-100% to +100% , depending on heat/cool output configuration). The control will assume a specific output
power when input errors occur.

• All except one of the possible displayed error messages are input related.

• If you see

[`Er5]

, cycle power to the controller. If the error persists, call the factory.

• Be aware of the difference between U.S and European thermocouple color/colour codes.

• Reversed polarity input leads is one of the most common errors.

• Incorrect software input choice at the Configuration Menu

[CnFG]

input

[``In]

prompt is another

common error.

When calling the factory for help, please have:

1. The model number of the control.

2. A photocopy of pages 51-58 with the settings from your control, if possible.

3. Specifications of devices directly interfaced with the control.

Configuration Menu

[``In]

Input Type

[`C_F]

Celsius/Fahrenheit

[``rL]

Input Range Low

[``rh]

Input Range High

[`Ot1]

Output 1 Function

[`Ot2]

Output 2 Function

[dISP]

Display Default

[ALtY]

Alarm Type

[AhYS}

Alarm Hysteresis

[`LAt]

Alarm Latch

[`SIL]

Alarm Silencing

[FAIL}

Failure Mode

[tIM]

Timer Function

[Strt]

Start Timer

[`rdY]

Timer Ready Band

[``St]

Signal Time

[SLOC]

Set Point Lockout

[`tAG]

Lockout Tag