More alarm functions, See table 11, P. 29 – Watlow Series 935B User Manual

Page 29: P. 29. if, Lat] [`sil] [`alo] [`ahi, No] [`yes] [`yes

Advertising
background image

Watlow Series 935B User’s Manual 29

SET

Latching alarm

Silence alarm

With this selection, an alarm
cannot be silenced at the 935B
front panel (unless the alarm
is latched [

[~LAt]

=

[yes]

],

and the alarm condition
no longer exists).

SET

A value from input Range Low to

[`AhI]

.

A value from

[`alo]

to input Range High

Alarm Low

Alarm High

An unlatched alarm self-clears
when actual temperature returns
to within the safe area.

At the Range Low value, a

,

press

displays

[`off]

and

[`ahi]

disables.

At the Range High value, a

.

press

displays

[`off]

and

[`ahi]

disables.

[`lat]

[`sIl]

[`alO]

[`ahI]

[``no]

[``no]

[`yes]

[`yes]

A latched alarm requires the
operator to press the

ß

key to clear after the actual
temperature returns to within
the safe area.

With this selection, an alarm
can be silenced by pressing the

ß]

key.

[yes]

provides automatic

alarm silencing on start up.

Table 11 (below) and Table 10 (p. 27) illustrate the Series 935B alarm features.

Table 11 - Alarm Functions

Table 11 - Alarm Functions