Boltek EFM-100 v.2 User Manual

Page 32

Advertising
background image

C H A P T E R 3 – C O N F I G U R I N G T H E S O F T W A R E

26

Setpoint

Delta Alarm Setpoint is the change of the electric field magnitude required to trigger a Delta Alarm.
For example, with a setpoint of 1 kV/m the Delta Alarm will activate if the field increases or

decreases by 1 kV/m or more within the set interval time.

Interval
Delta Alarm Interval is the time frame that the electric field level needs to change in order to trigger

the Delta Alarm. For example, with an interval of 60 seconds, and a setpoint of 1kV/m, the field

level needs to increase or decrease by 1kV/m or more within 60 seconds to active the Delta Alarm.

Delay

The Delta Alarm Delay is the length of time the field difference must remain higher than the setpoint

before the alarm is activated. If the electric field difference drops below the setpoint before the delay

expires the delay timer will be reset. For example, with a delay of 30 seconds and setpoint of 1 kV/m
the electric field difference must remain above 1 kV/m or below -1 kV/m for 30 seconds before the

alarm activates.

Duration
Delta Alarm Duration is the length of time the Delta Alarm will remain active once the Delta Alarm

is triggered.

WAV File Checkbox
Check the checkbox to enable the playing of WAV file sound when the Delta Alarm activates. Clear

the checkbox to disable the playing of the WAV sound.

WAV Filename
The WAV Filename is the file which will play out the computer speakers when the Delta Alarm is

activated.
Click on the Browse icon

to select the WAV file from a list.

Click on the Play icon

to listen to the selected WAV file

WAV Repeat Interval
Enter the number of seconds between repeats of the WAV sound.

Advertising