2 specifications, Specifications – Fire-Lite MS-4E Fire Alarm Control Panel User Manual

Page 11

Advertising
background image

MS-2 & MS-4 Series Manual — P/N 51512:G2 10/18/2011

11

Specifications

Product Description

Zone Enable/Disable (one per zone)

LED Indicators

Fire Alarm (one per zone)

Supervisory (one per zone)

Trouble (one per zone)

Maintenance (one per zone)

AC Power

NAC Disable

Zone Disable

NAC Fault

System Trouble

Power Trouble

Walktest

Alarm Silence

Earth Fault LED (on circuit board) lights if zero impedance between FACP and ground exist

Battery Fault (on circuit board)

Charger Fault (on circuit board)

Piezo sounder for alarm, trouble and supervisory

24 volt operation

Low AC voltage sense

Alarm Verification

NACs Programmable for:

Silence Inhibit

Auto-Silence

Strobe Synchronization

Selective Silence (horn-strobe mute)

Temporal or Steady Signal

Silenceable or Nonsilenceable

Automatic battery trickle charger

Silent or audible walktest capabilities

Optional NAC Class A converter module (MS-4 only)

Optional 4XTMF Transmitter Module (MS-2 and MS-4)

Optional 4XZMF Zone Relay Module (MS-4 only)

Optional 4XLMF Module for RZA-4XF Remote LED Annunciator (MS-4 only)

1.2 Specifications

AC Power - TB8

MS-2/MS-4: 120 VAC, 50/60 Hz, 2.3 amps
MS-2E/MS-4E: 240 VAC, 50 Hz, 1.15 amps
Wire size: minimum #14 AWG (2.0 mm

2

) with 600V insulation

Battery (sealed lead acid only) - J8

Maximum Charging Circuit - Normal Flat Charge: 27.6 VDC @ 0.8 amp
Maximum Charger Capacity: 18 Amp Hour battery (two 7 Amp Hour batteries can be housed in the
FACP cabinet. Larger batteries require a separate battery box such as the BB-17F.)