3 calculating the system current draw, 1 overview, Calculating the system current draw – Fire-Lite MS-4E Fire Alarm Control Panel User Manual

Page 47

Advertising
background image

MS-2 & MS-4 Series Manual — P/N 51512:G2 10/18/2011

47

Calculating the System Current Draw

Power Supply Calculations

5.3 Calculating the System Current Draw

5.3.1 Overview

The control panel must be able to power all internal and external devices continuously during the
non-fire alarm condition. To calculate the non-fire alarm load on the system power supply when
primary power is applied, use Calculation Column 1 in Table 5.3 on page 48. The control panel
must support a larger load current during a fire alarm condition. To calculate the fire alarm load on
the power supply, use Calculation Column 2 in Table 5.3 on page 48. The secondary power source
(batteries) must be able to power the system during a primary power loss. To calculate the non-fire
alarm load on the secondary power source, use Calculation Column 3 in Table 5.3 on page 48.

When calculating current draw and the battery size, note the following:

‘Primary’ refers to the main power source for the control panel

‘Secondary’ refers to the control panel’s backup batteries

All currents are given in amperes (A). Table 5.2 shows how to convert milliamperes and
microamperes to full amperes.

5.3.2 How to Use Table 5.3 on page 48 to Calculate System

Current Draw

Use Table 5.3 on page 48 to calculate current draws as follows:

1. Enter the quantity of devices in all three columns.
2. Enter the current draw where required. Refer to the Fire-Lite Device Compatibility Document

for compatible devices and their current draw.

3. Calculate the current draws for each in all columns.
4. Sum the total current for each column.
5. Copy the totals from Column 2 and Column 3 to Table 5.4 on page 49.

Following are the types of current that can be entered into Table 5.3 on page 48:

Calculation Column 1 - The primary supply current load that the control panel must
support during a non-fire alarm condition, with AC power applied.

Calculation Column 2 - The primary supply current load that the control panel must
support during a fire alarm condition, with AC power applied.

Calculation Column 3 - The standby current drawn from the batteries in a non-fire alarm
condition during a loss of AC power.

To convert...

Multiply

Example

Milliamperes (mA) to
amperes (A)

mA x 0.001

3 mA x 0.001 = 0.003A

Microamperes (

µ

A) to

amperes (A)

µ

A x 0.000001

300

µ

A x 0.000001 = 0.0003 A

Table 5.2 Converting to Full Amperes

Advertising