Fire-Lite MS-4E Fire Alarm Control Panel User Manual

Page 34

Advertising
background image

34

MS-2 & MS-4 Series Manual — P/N 51512:G2 10/18/2011

Program Options via DIP Switch

DIP Switch Settings

Switch Number

DIP Switch Number

DIP Switch ON

SW1

1

Silence Inhibit

2

Auto-silence

3

Temporal Coding

4

Selective Silence (if sync. enabled)

5

Trouble Reminder

6

AC Trouble Delay

7

Autoresettable Supervisory

8

IDC Combination
Waterflow/Supervisory Circuit

SW2

1

IDC1 Verification

2

IDC1 Supervisory

3

IDC2 Verification

4

IDC2 Supervisory

5

IDC3 Verification

6

IDC3 Supervisory

7

IDC4 Verification

8

IDC4 Supervisory

SW3

1

NAC1 Nonsilenceable

2

NAC1 Disable

3

NAC2 Nonsilenceable

4

NAC2 Disable

5 & 6

used to select strobe

synchronization feature as

shown to the right

Switch 5

Switch 6

No Synchronization

OFF

OFF

System Sensor Synchronization

ON

OFF

Gentex Synchronization

OFF

ON

Wheelock Synchronization

ON

ON

7

Nonsilenceable Waterflow for
Combination Circuit
(only if SW1 switch 8 is ON)

8

spare

Table 3.2 MS-4 DIP Switch Settings