MS-2 & MS-4 Series Manual — P/N 51512:G2 10/18/2011

33

DIP Switch Settings

Program Options via DIP Switch

3.1 DIP Switch Settings

The following tables list the programmable features for the MS-2 and MS-4. Placing a DIP switch
in the ON position will select the feature while placing the DIP switch in the OFF position will
deselect the feature. The exceptions to this rule are SW3 DIP switches 5 & 6. These two switches
are used to select the Notification Appliance Circuit synchronization feature. A detailed description
of each feature is presented in the following pages.

Important: When any programmable feature is changed by repositioning a DIP switch, the FACP
Reset button must be pressed to ensure that the control panel can read the new switch position.

Switch Number

DIP Switch Number

DIP Switch ON

SW1

1

Silence Inhibit

2

Auto-silence

3

Temporal Coding

4

Selective Silence (if sync. enabled)

5

Trouble Reminder

6

AC Trouble Delay

7

Autoresettable Supervisory

8

IDC Combination
Waterflow/Supervisory Circuit

SW2

1

not used

2

not used

3

IDC1 Verification

4

IDC1 Supervisory

5

IDC2 Verification

6

IDC2 Supervisory

7

not used

8

not used

SW3

1

NAC1 Nonsilenceable

2

NAC1 Disable

3

not used

4

not used

5 & 6

used to select strobe

synchronization feature as

shown to the right

Switch 5

Switch 6

No Synchronization

OFF

OFF

System Sensor Synchronization

ON

OFF

Gentex Synchronization

OFF

ON

Wheelock Synchronization

ON

ON

7

Nonsilenceable Waterflow for
Combination Circuit
(only if SW1 switch 8 is ON)

8

spare

Table 3.1 MS-2 DIP Switch Settings