4xzmf zone relay module (ms-4 only) – Fire-Lite MS-4E Fire Alarm Control Panel User Manual

Page 29

Advertising
background image

MS-2 & MS-4 Series Manual — P/N 51512:G2 10/18/2011

29

Installation of Optional Modules

Installation

4XZMF Zone Relay Module (MS-4 only)

The 4XZMF provides four zone alarm, one system alarm and one system trouble Form-C relays.
Nonpower-limited and power-limited wiring must have a minimum distance of 0.25”, wire to wire.
If this module is used to drive nonpower-limited and power-limited circuits, follow the instructions
below:

1. Skip a set of dry contacts to maintain the 0.25” required space between power-limited and

nonpower-limited circuits. The wiring of this module must follow the requirements as
specified in “Power-limited Wiring Requirements” on page 24.

OR

2. If this module is needed to drive power-limited and nonpower-limited relays that are next to

each other, refer to the following illustration which shows a typical connection:

Relay #1 through #4 will activate with

Output #1 through #4 and remain latched.

Use Disable Switch to
disconnect the relays

NO
NC
C
NO
NC
C
NO
NC
C
NO
NC
C
NO
NC
C
NO
NC
C

Relay #1

Relay #2

Relay #3

Relay #4

Alarm

Trouble

}

}

}

}

}

}

1
2
3
4
5
6
7
8
9
10
11
12
13
14
15
16
17
18

4xzma.wmf

power-limited circuit

power-limited circuit

}

}

}

}

NO

NC

C

NO

NC

C

NO

NC

C

NO

NC

C

Relay #1

Relay #2

Relay #3

Relay #4

{

{

{

{

no connection

Figure 2.14 4XZMF Zone Relay Module

4xzma.

w

m

f

nonpower-limited circuit

nonpower-limited circuit

Advertising