2.4.2 Special Application DC Power Output Connections

Resettable 24 VDC special application power is available on both the MS-2 and MS-4 control
panels. Nonresettable 24 VDC special application power is available only on the MS-4.

2.4.3 Relays

The MS-2 and MS-4 control panels provide an alarm and fail-safe trouble relay and the MS-4 also
provides a supervisory relay. Each Form-C relay is rated for 2 amps @ 30V

DC (resistive).

Note that relay connections may be power-limited or nonpower-limited, provided that 0.25”
minimum spacing is maintained between conductors of power-limited and nonpower-limited
circuits.

TB1

Figure 2.7 Special Application Power

4-Wire Smoke Detector Power (500 mA)
24 VDC filtered, resettable special application power for
4-wire smoke detectors can be obtained from these
terminals (power-limited)

Nonresettable Power (500 mA) -MS-4Only
24 VDC filtered, nonresettable special application power
can be obtained from
these terminals (power-limited)

+ - + -

ms-

4t

b

1.

wmf

TB
5

TB
6

TB
7

TROUBLE

C TRBL NORM

C NC NO

ALARM

SUPV

C NC NO

Figure 2.8 Relay Terminals

Note: Relay contacts are shown with
power applied to the panel and no active
troubles, alarms or supervisories.
The Trouble Relay is a fail-safe relay
which will transfer on any trouble or total
power failure.