Input Circuits

2.3 Input Circuits

The MS-2 has two IDCs (Initiating Device Circuits) and the MS-4 has four IDCs. Each circuit is
compatible with System Sensor’s i

3

smoke detectors which generate a maintenance signal when the

detector becomes dirty and a separate supervisory ‘freeze’ signal when ambient temperature falls
below the detector rating. The maximum loop resistance limit for each IDC is 100 ohms. The field
wiring for each zone is supervised for opens, shorts and ground faults (zero impedance to ground).
All conditions are visually and audibly annunciated.

Each circuit is configured for Style B (Class B) operation and will accept I

3

smoke detectors, any

normally-open contact devices as well as conventional 2-wire or 4-wire, 24 VDC smoke detectors.
In addition, Zone 1 (IDC 1) on the MS-2 and Zone 2 (IDC2) on the MS-4 can be programmed as
combination supervisory and waterflow zones. Refer to the Fire•Lite Device Compatibility
Document for a list of compatible devices.

MS-4 Initiating Device Circuits can be converted to Style D (Class A) by installing the optional
Class A Converter module. Refer to “CAC-4 Class A Converter Module (MS-4 only)” on page 25.

Figure 2.4 IDC Connections

Class B Initiating Device Circuits (supervised and power-limited)

4.7 K

, ½ watt resistor P/N:71252

UL listed
compatible
2-wire smoke
detectors

manual pull stations

heat detectors

Dummy load all
unused circuits - 4.7
K

, ½ watt resistor

(P/N: 71245)

Note: Zones 3 & 4 on
MS-4 only

ms-

4id

c.wmf

UL listed Power Supervision Relay

(refer to Device Compatibility Document for list of compatible relays)

Resettable 24 VDC
4-wire smoke
detector power
(500 mA maximum)

UL listed compatible 4-wire smoke detector