4 circuits, 5 components, 6 optional modules and accessories – Fire-Lite MS-4E Fire Alarm Control Panel User Manual

Page 14

Advertising
background image

14

MS-2 & MS-4 Series Manual — P/N 51512:G2 10/18/2011

Product Description

Circuits

1.4 Circuits

Input Circuits

Two input IDCs (Initiating Device Circuits) on the MS-2 and four IDCs on the MS-4 provide Style
B (Class B) configurations. All IDCs accept i

3

detectors as well as conventional two-wire smoke

detectors, four-wire smoke detectors and normally-open contact devices.

Output Circuits

24 VDC resettable special application power output - 500 mA

24 VDC nonresettable special application power output (MS-4 only) - 500 mA

24 volt battery charger (up to 18 Amp Hour batteries)

Notification Appliance Circuits

One NAC (Notification Appliance Circuit) Style Y (Class B) on the MS-2
Two NACs Style Y (Class B) on the MS-4

Relays

Alarm Relay
Trouble Relay (fail-safe)
Supervisory Relay (MS-4 only)
Form-C contacts rated 2.0 amps @ 30 V

DC (resistive)

1.5 Components

Main Circuit Board

The main circuit board contains the system’s CPU, power supply, other primary components and
wiring interface connectors. Optional modules plug in and are mounted to the main circuit board.

Cabinet

The backbox measures 14.5” (36.8 cm) x 15.218” (38.65 cm) x 2.875” (7.3 cm) and provides space
for two batteries (up to 7 Amp Hours). Also included is a dress panel which mounts inside the
cabinet.

Transformer Assembly

One 100VA transformer is provided standard with the FACP. An optional second 100VA
transformer is available for the MS-4 to provide maximum accessory power.

Batteries

The cabinet provides space for two 7 Amp Hour batteries (larger batteries up to 18 Amp Hour,
require use of a UL listed battery box such as the BB-17F). Batteries must be ordered separately.

1.6 Optional Modules and Accessories

CAC-4 Class A Converter Module (MS-4 only)

The CAC-4 Module can be used to convert the Style B (Class B) Initiating Device Circuits to Style
D (Class A) and Style Y (Class B) Notification Appliance Circuits to Style Z (Class A). The
module connects to J1 on the MS-4 main circuit board.

4XTMF Transmitter Module (MS-2 and MS-4)

The 4XTMF provides a supervised output for local energy municipal box transmitter and alarm and
trouble reverse polarity. It includes a disable switch and disable trouble LED. A module jumper
option allows the reverse polarity circuit to open with a system trouble condition if no alarm