1 fire alarm response, 2 fire alarm restoral, 3 system supervisory condition response – Fire-Lite MS-4E Fire Alarm Control Panel User Manual

Page 44: 4 system supervisory restoral response, 5 trouble condition response

Advertising
background image

44

MS-2 & MS-4 Series Manual — P/N 51512:G2 10/18/2011

Operating Instructions

Operation

4.4.1 Fire Alarm Response

The control panel will, upon detection of an alarm condition, cause the following:

Latch the alarm condition - requires panel reset to clear alarm condition

Blink the Zone Alarm LED one second On and one second Off

Turn on remote annunciator alarm LED and piezo sounder

Turn the Notification Appliance Circuit(s) on

Turn the FACP piezo sounder on steady

Turn on the alarm relay

Start the Silence Inhibit, Auto-silence and Trouble Reminder functions if enabled

4.4.2 Fire Alarm Restoral

The control panel returns to normal after all alarms have been cleared and a system reset button has
been pressed (pull stations have been reset, smoke detectors have reset and no smoke is present,
waterflow has stopped). The control panel will perform the following upon restoral of all active
alarms:

Turn off the FACP Zone Alarm LED

Turn off remote annunciator alarm LED and piezo sounder

Turn off the Notification Appliance Circuit(s)

Turn off the FACP piezo sounder

Turn off the alarm relay

i

3

smoke detectors will be polled for maintenance and freeze conditions on initial entry into

Normal mode. Thereafter, each device will be polled every hour for freeze and every four
hours for maintenance conditions

4.4.3 System Supervisory Condition Response

Zones can be programmed for supervisory in applications where a waterflow sensing device has
been employed and a sprinkler tamper switch is to be monitored. An I

3

detector in a ‘freeze’

condition (detected abnormally low ambient temperature) will also generate a supervisory
condition on its alarm zone (refer to the I

3

specification sheet for temperature threshold). Any

supervisory condition will cause the control panel to perform the following functions:

Blink the FACP Zone Supervisory LED ½ second On and ½ second Off

Pulse the piezo sounder ½ second On and ½ second Off

Turn on the supervisory relay (MS-4 only)

4.4.4 System Supervisory Restoral Response

When the supervisory condition has been cleared, the control panel will perform the following:

Turn off the FACP Zone Supervisory LED

Turn off the piezo sounder

Turn off the supervisory relay (MS-4 only)

4.4.5 Trouble Condition Response

The control panel, upon detection of one or more trouble conditions, well perform the following:

Blink the FACP System Trouble LED one second On and one second Off

Blink the FACP Zone Trouble LED one second On and one second Off

Turn on remote annunciator Trouble LED and pulse the piezo sounder