MS-2 & MS-4 Series Manual — P/N 51512:G2 10/18/2011

Installation

Installation of Optional Modules

circuit. Do not wire to the corresponding A+ and A- terminals on the CAC-4 module. Note that
Zone 1 IDC on the MS-2 and Zone 2 IDC on the MS-4 can be configured as a combination
waterflow/supervisory circuit as illustrated in the following figure.

2.6.2 4XTMF, 4XLMF and 4XZMF Option Modules

MS-4: The 4XLMF LED Interface Module can only be plugged into connectors J3 and J5 on the
MS-4 main circuit board. The 4XTMF and 4XZMF modules can be plugged into connectors J3
and J5 or J4 and J6 on the MS-4 main circuit board. A combination of any two of the three
modules can be installed.

MS-2: Only the 4XTMF module can be plugged into connectors J3 & J5 on the MS-2 main circuit
board. (No other option modules can be installed on the MS-2).

Figure 2.11 Wiring NACs and IDCs for Class A Operation

CAC-4 Class A Converter Module

MS-4
Circuit Board

Class B (Style B)

IDC - 4.7 K

½ watt ELR

resistor

P/N:71252

(supervised and

power-limited)

Dummy load all unused
circuits - 4.7 K

½ watt ELR resistor
(P/N: 71245)

Polarized

Bell

Circuit polarities
shown in alarm
condition

Class A (Style Z) NAC

(supervised and power-limited)

Class A

(Style D) IDC

(supervised and

power-limited)

Class A

(Style D) IDC

Combo Waterflow &

Supervisory

20K

, ½ watt ELR

resistor P/N:75477

(supervised and

power-limited)

1.2 K

½ watt

In-Line

resistor

P/N:75579

Polarized

Strobe

Polarized

Horn

Tamper

Tamper

Waterflow

Smoke

Smoke

Pull

Station

Pull

Station

Heat

Heat

IMPORTANT! All

devices must be

within 20 feet of the

Class A portion of

the circuit and

wiring must be in

conduit.