Allied Air Enterprises 80G1UH User Manual

Page 12

Advertising
background image

506526-01

Page 12 of 39

Issue 1031

Filters

This unit is not equipped with a filter or rack. A field provided

high velocity filter is required for the unit to operate properly.

Table 1 lists recommended filter sizes.

A filter must be in place any time the unit is operating.

Duct System

Use industry approved standards (such as those published

by Air Conditioning Contractors of America or American

Society of Heating, Refrigerating and Air Conditioning

Engineers) to size and install the supply and return air duct

system. This will result in a quiet and low static system that

has uniform air distribution.

NOTE: Do not operate the furnace in the heating mode

with an external static pressure that exceeds 0.8 inches w.c.

Higher external static pressures may cause erratic limit

operation.

Supply Air Plenum

If the furnace is installed without a cooling coil, a removable

access panel must be installed in the supply air duct. The

access panel should be large enough to permit inspection

(either by smoke or reflected light) of the heat exchanger

for leaks after the furnace is installed. The furnace access

panel must always be in place when the furnace is operating

and it must not allow leaks into the supply air duct system.

Return Air Plenum

NOTE: Return air must not be drawn from a room where

this furnace, or any other gas fueled appliance (i.e., water

heater), or carbon monoxide producing device (i.e., wood

fireplace) is installed.

When return air is drawn from a room, a negative pressure

is created in the room. If a gas appliance is operating in a

room with negative pressure, the flue products can be pulled

back down the vent pipe and into the room. This reverse

flow of the flue gas may result in incomplete combustion

and the formation of carbon monoxide gas. This toxic gas

might then be distributed throughout the house by the furnace

duct system.

In upflow applications, the return air can be brought in through

the bottom or either side of the furnace. If a furnace with

bottom return air is installed on a platform, make an airtight

seal between the bottom of the furnace and the platform to

ensure that the unit operates properly and safely. Use

fiberglass sealing strips, caulking, or equivalent sealing

method between the plenum and the furnace cabinet to

ensure a tight seal. If a filter is installed, size the return air
duct to fit the filter frame.

WARNING

The inner blower panel must be securely in place when

the blower and burners are operating. Gas fumes,

which could contain carbon monoxide, can be drawn

into living space resulting in personal injury or death.

Figure 14

Horizontal Application

Unit installed on Platform

Table 1

WARNING

Improper installation of the furnace can result in personal

injury or death. Combustion and flue products must

never be allowed to enter the return air system or the

living space. Use screws and joint tape to seal the return

air system to the furnace.

In platform installations with bottom return air, the furnace

should be sealed airtight to the return air plenum. A

door must never be used as a portion of the return air

duct system. The base must provide a stable support

and an airtight seal to the furnace. Allow absolutely no

sagging, cracks, gaps, etc..

The return and supply air duct systems must never be

connected to or from other heating devices such as a

fireplace or stove, etc.. Fire, explosion, carbon

monoxide poisoning, personal injury and/or property

damage could result.

Advertising
This manual is related to the following products: