Allied Air Enterprises 80G1UH User Manual

Page 6

Advertising
background image

506526-01

Page 6 of 39

Issue 1031

General

These instructions are intended as a general guide and do

not supersede local codes in any way. Consult authorities

having jurisdiction before installation.

In addition to the requirements outlined previously, the

following general recommendations must be considered

when installing one of these furnaces:

Place the furnace as close to the center of the air

distribution system as possible. The furnace should also

be located close to the chimney or vent termination point.

Do not install the furnace where drafts might blow directly

into it. This could cause improper combustion.

Do not block the furnace combustion air openings with

clothing, boxes, doors, etc. Air is needed for proper

combustion and safe unit operation.

When the furnace is installed in an attic or other insulated

space, keep insulation away from the furnace.

NOTE: The Commonwealth of Massachusetts stipulates

these additional requirements:

Gas furnaces shall be installed by a licensed plumber

or fitter only.

The gas cock must be “T handle” type.

When a furnace is installed in an attic, the passageway

to and service area surrounding the equipment shall be
floored.

Combustion, Dilution & Ventilation Air

In the past, there was no problem in bringing in sufficient

outdoor air for combustion. Infiltration provided all the air

that was needed. In today’s homes, tight construction

practices make it necessary to bring in air from outside for

combustion. Take into account that exhaust fans, appliance

vents, chimneys, and fireplaces force additional air that could

be used for combustion out of the house. Unless outside

air is brought into the house for combustion, negative

pressure (outside pressure is greater than inside pressure)

will build to the point that a downdraft can occur in the furnace

vent pipe or chimney. As a result, combustion gases enter

the living space creating a potentially dangerous situation.

In the absence of local codes concerning air for combustion

and ventilation, use the guidelines and procedures in this

section to install these furnaces to ensure efficient and safe

operation. You must consider combustion air needs and

requirements for exhaust vents and gas piping.

A portion of this information has been reprinted with

permission from the National Fuel Gas Code (ANSI-Z223.1).

This reprinted material is not the complete and official

position of the ANSI on the referenced subject, which is

represented only by the standard in its entirety.

Product Contains Fiberglass Wool.

Disturbing the insulation in this product during

installation, maintenance, or repair will expose you to

fiberglass wool. Breathing this may cause lung cancer.

(Fiberglass wool is known to the State of California to

cause cancer.)

Fiberglass wool may also cause respiratory, skin, and

eye irritation.

To reduce exposure to this substance or for further

information, consult material safety data sheets available

from address shown below, or contact your supervisor.

Allied Air Enterprises, Inc.

215 Metropolitan Drive

West Columbia, SC 29170

WARNING

Insufficient combustion air can cause headaches,

nausea, dizziness or asphyxiation. It will also cause

excess water in the heat exchanger resulting in rusting

and premature heat exchanger failure. Excessive

exposure to contaminated combustion air will result in

safety and performance related problems. Avoid

exposure to the following substances in the combustion

air supply:

Permanent wave solutions

Chlorinated waxes and cleaners

Chlorine base swimming pool chemicals

Water softening chemicals

De-icing salts or chemicals

Carbon tetrachloride

Halogen type refrigerants

Cleaning solvents (such as perchloroethylene)

Printing inks, paint removers, varnishes, etc.

Hydrochloric acid

Antistatic fabric softeners for clothes dryers

Masonry acid washing materials

WARNING

Advertising
This manual is related to the following products: