Allied Air Enterprises 80G1UH User Manual

Page 15

Advertising
background image

506526-01

Page 15 of 39

Issue 1031

Once the venting system is installed, attach the

“Disconnected Vent” warning sticker to a visible area of

the plenum near the vent pipe. See Figure 23. The

warning sticker is provided in the bag assembly. Order

kit 66W04 for additional stickers.

IMPORTANT

These series units are classified as fan assisted Category I

furnaces when vertically vented according to the latest edition

of National Fuel Gas Code (NFPA 54 / ANSI Z223.1) in the

USA. A fan assisted Category I furnace is an appliance

equipped with an integral mechanical means to either draw

or force combustion products through the combustion

chamber and/or heat exchanger. This unit is not approved

for use with horizontal venting.

NOTE: Use these instructions as a guide. They do not

supersede local codes. This furnace must be vented

according to all local codes these installation instructions,

and the provided venting tables in these instructions.

The venting tables in this manual were extracted from the

National Fuel Gas Code (NFPA 54 / ANSI Z223.1) and are

provided as a guide for proper vent installation. Proper

application, termination, construction and location of vents

must conform to local codes having jurisdiction. In the

absence of local codes, the NFGC serves as the defining

document.

Refer to the tables and the venting information contained in

these instructions to properly size and install the venting

system.

Asphyxiation hazard. The exhaust vent for this furnace

must be securely connected to the furnace flue transitiion

at all times.

WARNING

Figure 23

Vent Connection

Use self drilling sheet metal screws or a mechanical fastener

to firmly secure the vent pipe to the round collar of the flue

transition. If self drilling screws are used to attach the vent

pipe, it is recommended that three be used. Drive one self

drilling screw through the front and one through each side

of the vent pipe and collar. See Figure 23.

Install the first vent connector elbow at a minimum of six

inches (152 mm) from the furnace vent outlet. See Figure

23.

Venting Using a Masonry Chimney

The following additional requirements apply when a lined

masonry chimney is used to vent this furnace.

Masonry chimneys used to vent Category I central furnaces

must be either tile lined or lined with a listed metal lining

system or dedicated gas vent. Unlined masonry chimneys

are prohibited. See Figures 24 and 25 for common venting.

A chimney with one or more sides exposed to the outside of

the structure is considered to be an exterior chimney.

An exterior masonry chimney that is not tile lined must be

lined with B1 vent or a listed insulated flexible metal vent.

An exterior tile lined chimney that is sealed and capped may

be lined with a listed uninsulated flexible metal vent.

If the existing chimney will not accommodate a listed metal

liner, either the chimney must be rebuilt to accommodate

one of these liners or an alternate approved venting method

must be found.

Insulation for the flexible vent pipe must be an encapsulated

fiberglass sleeve recommended by the flexible vent pipe

manufacturer. See Figure 24.

Figure 24

Common Venting Using Metal Lined

Masonry Chimney

NOTE 1: Refer to the provided venting tables for installations.

Refer to the capacity requirements shown in the provided venting

tables.

Advertising
This manual is related to the following products: