Allied Air Enterprises 80G1UH User Manual

Page 17

Advertising
background image

506526-01

Page 17 of 39

Issue 1031

6. The entire length of single wall metal vent connector

shall be readily accessible for inspection, cleaning, and

replacement.

7. Single appliance venting configurations with zero lateral

lengths (Tables 3 and 4) are assumed to have no elbows

in the vent system. For all other vent configurations,

the vent system is assumed to have two 90° elbows.

For each additional 90° elbow or equivalent (for example

two 45° elbows equal one 90° elbow) beyond two, the

maximum capacity listed in the venting table should be

reduced by 10% (0.90 x maximum listed capacity).

8. The common venting Tables (5, 6,7, and 8) were

generated using a maximum horizontal vent connector

length of 1-1/2 feet (.46 m) for each inch (25 mm) of

connector diameter as follows:

Table 2

9. If the common vertical vent is offset, the maximum

common vent capacity listed in the common venting

tables should be reduced by 20%, the equivalent of two

90° elbows (0.80 x maximum common vent capacity).

The horizontal length of the offset shall not exceed

1-1/2 feet (.46 m) for each inch (25 mm) of common

vent diameter.

10. The vent pipe should be as short as possible with the

least number of elbows and angles required to complete

the job. Route the vent connector to the vent using the

shortest possible route.

11. A vent connector shall be supported without any dips or

sags and shall slope a minimum of 1/4 inch (6.4 mm)

per linear foot (305 mm) of connector, back toward the

appliance.

12. Vent connectors shall be firmly attached to the furnace

flue collar by self drilling screws or other approved

means,except vent connectors of listed type B vent

material which shall be assembled according to the

manufacturer’s instructions. Joints between sections

of single wall connector piping shall be fastened by

screws or other approved means.

13. When the vent connector used for Category I appliances

must be located in or pass through a crawl space, attic

or other areas which may be cold, that portion of the

vent connector shall be constructed of listed doublewall

type B vent material or material having equivalent

insulation qualities.

14. All venting pipe passing through floors, walls, and

ceilings must be installed with the listed clearance to

combustible materials and be fire stopped according to

local codes. In absence of local codes, refer to NFGC

(2223.1 ).

15. No portion of the venting system can extend into, or

pass through any circulation air duct or plenum.

16. Vent connectors serving Category I appliances shall not

be connected to any portion of mechanical draft systems

operating under positive pressure such as Category III

or IV venting systems.

17. If vent connectors are combined prior to entering the

common vent, the maximum common vent capacity

listed in the common venting tables must be reduced by

10%, the equivalent of one 90° elbow (0.90 x maximum

common vent capacity).

18. The common vent diameter must always be at least as

large as the largest vent connector diameter.

19. In no case, shall the vent connector be sized more than

two consecutive table size diameters over the size of

the draft hood outlet or flue collar outlet.

20. Do not install a manual damper, barometric draft

regulator or flue restrictor between the furnace and the

chimney.

21. When connecting this appliance to an existing dedicated

or common venting system, you must inspect the venting

system’s general condition and look for signs of

corrosion. The existing vent pipe size must conform to

these instructions and the provided venting tables. If

the existing venting system does not meet these

requirements, it must be resized.

Advertising
This manual is related to the following products: