Allied Air Enterprises 80G1UH User Manual

Page 16

Advertising
background image

506526-01

Page 16 of 39

Issue 1031

DO NOT insulate the space between the liner and the

chimney wall with puffed mica or any other loose granular
insulating material.

SINGLE appliance venting of a fan assisted furnace into

a tile lined masonry chimney (interior or outside wall) is

prohibited. The chimney must first be lined with either

type B1 vent or an insulated single wall flexible vent

lining system which has been sized according to the

provided venting tables and the vent pipe manufacturer’s

instructions.

IMPORTANT

A fan assisted furnace may be commonly vented into an

existing lined masonry chimney if the following conditions

are met:

The chimney is currently serving at least one drafthood

equipped appliance.

The vent connectors and chimney are sized according

to the provided venting tables.

If type B1 double wall vent is used inside a chimney, no

other appliance can be vented into the chimney. The outer

wall of type B1 vent pipe must not be exposed to flue

products. A type B1 vent or masonry chimney liner shall

terminate above the roof surface with a listed cap or a’iisted

roof assembly according to the terms of their respective

listings and the vent manufacturer’s instructions.

When inspection reveals that an existing chimney is not safe

for the intended purpose, it shall be rebuilt to conform to

nationally recognized standards, lined or relined with suitable

materials, or replaced with a gas vent or chimney suitable

for venting. The chimney passageway must be checked

periodically to ensure that it is clear and free of obstructions.

Do not install a manual damper, barometric draft regulator,

or flue restrictor between the furnace and the chimney.

Never connect a Category I appliance to a chimney that is

servicing a solid fuel appliance. If a fireplace chimney flue

is used to vent this appliance, the fireplace opening must be

permanently sealed.

A type B or listed chimney lining system that passes through

an unused masonry chimney flue is not considered to be

exposed to the outdoors.

General Venting Requirements

Vent all furnaces according to these instructions:

1. Vent diameter recommendations and maximum

allowable piping runs are found in the provided venting

tables.

2. In no case should the vent or vent connector diameter

be less than the diameter specified in the provided

venting tables.

3. The minimum vent capacity determined by the sizing

tables must be less than the low fire input rating and the

maximum vent capacity must be greater than the high

fire input rating.

4 . Single appliance vents - If the vertical vent or tile lined

chimney has a larger diameter or flow area than the

vent connector, use the vertical vent diameter to

determine the minimum vent capacity and the vent

connector diameter to determine the maximum vent

capacity. The flow area of the vertical vent, however,

shall not exceed 7 times the flow area of the listed

appliance categorized vent area, drafthood outlet area

or flue collar area unless designed according to

approved engineering methods.

5. Multiple appliance vents - The flow area of the largest

section of vertical vent or chimney shall not exceed 7

times the smallest listed appliance categorized vent

area, drafthood outlet area or flue collar area unless

designed according to approved engineering methods.

Common Venting Using Tile Lined Interior Masonry Chimney and Combined Vent Connector

NOTE: Refer to provided venting

tables for installations.

NOTE: The chimney must be properly sized

per provided venting tables or lined with

listed metal lining system.

Figure 25

Advertising
This manual is related to the following products: