Allied Air Enterprises 80G1UH User Manual

Page 22

Advertising
background image

506526-01

Page 22 of 39

Issue 1031

Removal of the Furnace from Common Vent

In the event that an existing furnace is removed from a

venting system commonly run with separate gas appliances,

the venting system is likely to be too large to properly vent

the remaining attached appliances.

Conduct the following test while each appliance is operating

and the other appliances (which are not operating) remain

connected to the common venting system. If the venting

system has been installed improperly, you must correct the

system as indicated in the general venting requirements
section.

The following steps shall be followed for each appliance

connected to the venting system being placed into operation,

while all other appliances connected to the venting system

are not in operation:

1. Seal any unused openings in the common venting

system.

2. Inspect the venting system for proper size and horizontal

pitch. Determine that there is no blockage, restriction,

leakage, corrosion, or other deficiencies which could

cause an unsafe condition.

3. Close all building doors and windows and all doors

between the space in which the appliances remaining

connected to the common venting system are located

and other spaces of the building. Turn on clothes dryers

and any appliances not connected to the common

venting system. Turn on any exhaust fans, such as

range hoods and bathroom exhausts, so they will

operate at maximum speed. Do not operate a summer

exhaust fan. Close fireplace dampers.

4. Follow the lighting instructions. Turn on the appliance

that is being inspected. Adjust the thermostat so that

the appliance operates continuously.

5. After the burners have operated for 5 minutes, test for

leaks of flue gases at the draft hood relief opening. Use

the flame of a match or candle.

6. After determining that each appliance connected to the

common venting system is venting properly, (step 3)

return all doors, widows, exhaust fans, fireplace

dampers, and any other gas burning appliances to their

previous mode of operation.

7. If a venting problem is found during any of the preceding

tests, the common venting system must be modified to

correct the problem.

Resize the common venting system to the minimum vent

pipe size determined by using the appropriate tables in

Appendix G. (These are in the current standards of the

National Fuel Gas Code ANSI 2223.1.

CARBON MONOXIDE POISONING HAZARD

Failure to follow the steps outlined below for each

appliance connected to the venting system being placed

into operation could result in carbon monoxide poisoning

or death.

WARNING

Advertising
This manual is related to the following products: