With RS-485 and RS-422 interfaces, termination resistors need to be
used at both ends of the line, if data rate is 9600 Bd or higher and
distance is 600 m (2000 ft) or longer. Resistor range 100 ... 180

Ω

is

suitable for twisted pair lines. Resistors are connected across RX- to
RX+ and across TX- to TX+ (with two-wire RS-485 only one resistor
needed).