Wiring, Controller module (fmmp01), Relay output module (fmor01) – AMETEK 2120 PLC Interface Module User Manual

Page 14

Advertising
background image

10

Installation and Programming Manual

Chapter 3: Mounting and Wiring

This section contains pinout diagrams for each module. System wiring diagrams follow.

Controller Module (FMMP01)

The controller has two connectors: a D9 connector (J1) for RS-232 and RS-485 serial
communications, and a program lockout connector (J2) intended for a keyswitch. (See Figure
3-2). Making connections to both connectors is optional. However, the program lockout
connector must be jumpered to allow the unit to enter program mode. J2’s input rating is +5
VDC maximum dry contact or open collector (drain) only. Actuation voltage must be less than
+1.0 VDC at 0.2 mA. The terminal wire size is No. 22-12 AWG.

Figure 3-2 Controller Pinout Diagram

Drawing E8002099

NOTE: The controller’s program lockout connector (J2) must be jumpered to allow the unit

to enter program mode.

Relay Output Module (FMOR01)

The relay output module contains two overtravel limit relays. Each relay contains a N.O. contact
pair and a separate N.C. contact pair. (See Figure 3-3). The relay contacts are rated at 8 amps
250 VAC, 30 VDC, 1/4 HP 125, 250 VAC. The terminal wire size is 22-12 AWG.

COMMUNICATIONS CONNECTOR

PIN SIGNAL NAME DIRECTION

OUTPUT

INPUT

INPUT

OUTPUT

4

NO CONNECTION

9

8

7

6

5

CTS RS-232

TX2- RS-485

GND SIGNAL

RTS RS-232

TX2+ RS-485

I / O

I / O

3

2

1

GND CHASSIS

RXD RS-232

TXD RS-232

{

(J2)

INPUT -

INPUT +

PIN 6

CONNECTOR D9 FEMALE

COMMUNICATIONS (J1)

PIN 9

PIN 1

FMMP01

2

1

PIN 5

C.P.U.

3.2: Wiring