Appendix A: Error Messages

Error Conditions (306)

If the monitor displays “SEr320” one of four error conditions relating to the resolver has
occurred. These conditions include primary open, primary shorted, S1, and S4 open or shorted.
To have the monitor display the error condition which has occurred, perform the following
steps:

1. Select the function key.

The monitor displays “F-----”.

2. Select function number 306. Select the enter key.

The monitor will display the exact condition which has occurred. The

following are the possible errors:

P OPEn (Primary Open)
P Shrt (Primary Shorted)
S4OPEn (S4 Open)

S1OPEn (S1 Open)

306

Chart A-7 LDT-Specifi c Error

Error Displayed

Error Description

Solution

SEr331

An error has occurred on the input device.
Fault pulse received from LDT.

Correct this error by placing the
magnet assembly back into the
active stroke area, and clear the
error.