AMETEK 2120 PLC Interface Module User Manual

Page 42

Advertising
background image

38

Installation and Programming Manual

Chapter 4: Programming

3. Enter either 0 or 1.

0 = Latch (default)
1 = Synchronize

Select the enter key.

Enter either
0 or 1

Enter either
0 or 1

202

2. Enter function 201. Select the enter key.

The monitor displays the function’s current value.

Logic Level (202)

This function will set up selection of either high true or low true logic.

1. Select the function key.

The monitor displays “F-----”

2. Enter function 202. Select the enter key.

The monitor displays the function’s current value.

3. Enter either 0 or 1.

0 = Low True
1 = High True (default)

Select the enter key.

Error Condition Output State (203)

This function allows you to select how the digital outputs will react to a failure in the Interface
Module, transducer and/or cable. The following three options describe what will happen on a
failure.

1. Select the function key.

The monitor displays “F-----”

2. Enter function 203. Select the enter key.

The monitor displays the function’s current value.

3. Enter either 0, 1 or 2.

0 = All Outputs Off (default)
1 = All Outputs On
2 = Last Valid Position

Select the enter key.

0, 1 or 2

203

Enter either

201

(F)

(F)