Appendix D: Specifi cations

55

RS-232 Output: Up to 115.2K baud, not less than ±5V into a 3K ohm, 2250

pF load.

Shock and Vibration: Tested up to MIL-STD 810E, method 514.4 category 10,

20-2K Hz., at 2G sine, 0.04 G

2

/Hz random and UL 491,

SA19, 10-150 Hz 10G sine.

Temperature Range:
Operating 32°F - 131°F (0°C - 55°C)
Storage 0°F - 150°F (-18°C - 66°C)

Digital:
Output Rating:
Sinking Device (option D1) 5 - 24 VDC @ 100mA max
V

OL

= 1.1V max

Sourcing Device (option D2) 5 - 24 VDC @ 100mA max
V

OH

= V

IN

- 1.8

TTL Device (option D3) V

OH

= 3.7 min @ I

OH

= 24mA

V

OL

= .44 max @ I

OL

= 24mA

Input Ratings: 24VDC @ 9mA max
Low < 1.4V @ 0.5mA
High > 2.0V @ 1mA
TTL Compatible

Power Requirements: 85-265 VAC, 50-60 Hz., internally fused at 1.5 amps.

Program Mode Input: Dry contact, open collector (drain) only; +5 VDC

maximum, current 0.2 mA.

Relay Contact Ratings: All relays are rated UL and CSA of 1/4 HP, 125-250 VAC;

8A 250 VAC, 30 VDC, shock resistant to 10 G.

RS-485 Output: Up to 115.2K baud, not less than ±1.5V into a 27 ohm load

(RS-485); not less than ±2.0V into a 50 ohm load (RS-422).
Maximum cable length of 1000' using a shielded twisted
pair cable (similar to a BELDEN 9481 cable)

NOTE: Digital output update time increases in analog confi guration from 100 to 125 µS