42

Installation and Programming Manual

Chapter 4: Programming

Analog output channel 2 is programmed using the same basic sequences except with the function
numbers noted below. Remember that the X shown in the function number represents the slot in
which the analog output board is installed in the Interface Module chassis.

Analog Output Channel 2 - Function numbers

A)

Select analog output based on position or velocity

Function No. X07

B)

Select voltage or current output

Function No. X10

C)

Scaling analog output

- Select minimum position/velocity value

Function No. X08

- Select analog output value to be linked to minimum position/velocity value

Function No. X11

- Select maximum position/velocity value

Function No. X09

- Select analog output value to be linked to maximum position/velocity value

Function No. X12

Analog output channel 1 will now provide a 2 to 8 VDC output as RPM increases between 500
and 2000 RPM. RPM values below 500 RPM will result in a 2 VDC analog output. RPM values
above 2000 RPM will result in an 8 VDC output.