Installation and Programming Manual

Chapter 4: Programming

41

4. Enter function number X02. Select enter key.

The monitor displays current minimum RPM value.

5. Enter 500. Select enter key. This sets minimum RPM value at 500 RPM.

The monitor displays 000500.

6. Select function key.

The monitor displays “F----”.

7. Enter function number X05. Select enter key.

The monitor displays current voltage output value linked to minimum RPM

value.

8. Enter 2. Select enter key. This sets a minimum voltage output value of 2VDC

for 500 RPM or less.

The monitor displays 002000.

9. Select function key.

10. Enter function number X03. Select enter key.

The monitor displays current maximum RPM value.

11. Enter 2000. Select enter key. This sets maximum RPM value at 2000 RPM.

The monitor displays 002000.

12. Select Function key.


The monitor displays “F-----”.

13. Enter function number X06. Select enter key.

The monitor displays current voltage output value linked to maximum RPM

value.

14. Enter 8. Select enter key. This sets a maximum voltage output value of 8VDC

at 2000RPM or more.

The monitor displays 008000.

X02

Enter
000500

X05

Enter
002000

X03

Enter
002000

X06

Enter
008000