Aalborg SDPROCs User Manual

Page 20

Advertising
background image

15

The same is true for 0 seconds, pressing the (-) button will rollover time settings to
99999 seconds. Press the ENTER button under MULT on the display, to change the
value of the multiplier to 10. Continuing to press the ENTER button under MULT on the
display, will change the value of the multiplier first to 100 and then back to 1. When
complete with TIME settings for the first step of the Batch program, press the ESC but-
ton under NEXT on the display, to go to the SETPOINT screen. The following display
will appear.

Set Point Settings for first step of the BATCH table

Pressing (+) or (-) will increment or decrement the step set point settings per 0.1%
F.S. respectively. When complete with SET POINT settings for the first step of the Batch
program, press the ENTER button under NEXT on the display, to go to the next step.
Continue with Time and Set point settings for as many steps as required for your appli-
cation (16 is the maximum limit). When complete with all settings for the Batch pro-
gram press the Esc button under EXIT on the display, to go to the BATCH control
screen. The following display will appear.

BATCH mode control screen with batch disabled

The two digit numbers after “SE:” indicate the number of the enabled steps for execu-
tions. Press the UP button under STEPS on the display, to change number of steps
from the batch program to be executed. With 16 steps enabled on the screen, press-
ing the Up button one more time will rollover the number of steps back to 1. Press the
ENTER button under LOOP on the display, to toggle the loop control ON and OFF. If
loop control is ON, after executing the last enabled step, the program will go back to
the first step and go on again until the loop mode will be disabled. NOTE: In order to
start batch program executions, press the Down button under START on the display.
NOTE: In order to execute a batch program, the valve control reference has to be set
to BATCH mode (See section e.2.6.1). The following display will appear.

BATCH mode control screen with batch enabled

Press the Down button under STOP on the display one more time, to toggle the batch
mode to OFF (disabled). Press the Esc button under EXIT on the display, to go to the
Main Display.