Aalborg SDPROCs User Manual

Page 27

Advertising
background image

22

change the decimal point to any desired digit, next move the cursor to the required
position, and adjust it to the decimal point with the (+) or (-) button. When complete
with Full Scale Flow Rate settings, press the ESC button under NEXT on the display, to
go to the Relays Assignment screen. The following Setup Relays Assignment Display
will appear.

e.3.7.5 Setup Relays Assignment Display

Two sets of dry contact relay are available for each channel. Each relay individually
can be assigned for:

= NO ACTION

= ALARM LOW

= ALARM HIGH

= TOTALIZER STOP

Press either the UP or DN button to change the relay assignment. When complete with
the first relay settings, press the ESC button under NEXT on the display, to go to the
second relay. The following display will appear.

Press the ESC button under NEXT on the display or the ENTER button under EXIT on
the display, to go back to the Main Display.

e.3.8 Setup Alarm Display

Before enabling the Alarm make sure all alarm settings are configured properly. High
and Low alarm values have to be entered in %F.S. engineering units. ALARM condi-
tions become valid when the difference between current readings and installed set
points is equal or more than corresponding values of high and low alarm levels. From
the Setup Channel Display (see section e.3.7) press the Up button under ALARM on
the display in order to make Alarm settings. The following Setup Alarm Mode Display
will appear.

e.3.8.1 Setup Alarm Mode Display

To change the Alarm Mode in ENABLED or DISABLED, press the button (UP, DOWN
respectively) directly below the mode shown on the display. Press the ENTER button
under EXIT on the display, to go back to the Main Display. Press the ESC button under