Aalborg SDPROCs User Manual

Page 28

Advertising
background image

23

NEXT on the display to go to the Alarm Low settings. The following Setup Alarm Low
Display
will appear.

e.3.8.2 Setup Alarm Low Display

Pressing (+) or (-) will increment or decrement Low Alarm settings per 0.1% F.S.
respectively. If no settings are required for High Alarm press the ENTER button under
EXIT on the display, to go back to the Main Display. Press the ESC button under NEXT
on the display to go to the Alarm High settings. The following Setup Alarm Low
Display
will appear.

e.3.8.3 Setup Alarm High Display

Pressing (+) or (-) will increment or decrement High Alarm settings per 0.1% F.S.
respectively. If no settings are required for High Alarm press the ENTER button under
EXIT on the display, to go back to the Main Display. Press the ESC button under NEXT
on the display to go to the Alarm Delay settings. The following Setup Alarm Delay
Display
will appear.

3.8.4 Setup Alarm Delay Display

Alarm Delay specifies the time interval in seconds the Alarm conditions have to be True
(without any interruption) before the Alarm will be activated. If zero value is set, the
Alarm will be activated immediately after Alarm conditions are met. Pressing (+) or (-)
will increment or decrement Alarm Delay settings per 1 second respectively. If no set-
tings are required for Alarm Action press the ENTER button under EXIT on the display,
to go back to the Main Display. Press the ESC button under NEXT on the display to go
to the Alarm Action settings. The following Setup Alarm Action Display will appear.

e.3.8.5 Setup Alarm Action Display

To change Alarm Action in NONE, BUZZER or VALVE, press the button (ESC, UP, DOWN
respectively) directly below the text shown on the display. If Buzzer action is chosen
the audible signal will be activated when Alarm conditions become true.

Advertising