Aalborg SDPROCs User Manual

Page 43

Advertising
background image

38

No Type

Description

Command Argument 1 Argument 2 Argument 3 Argument 4

Return string

9

Single Data
Request Returns
a string
containing readings
in %F.S. for all
available channels.

SD

NON

String with current
reading in %F.S
for all channels.
If channel not
calibrated [*]
will be added
to the reading.

10

Turns ON/OFF the
16 bit check sum
transmission of
check sums with
the data packet.
MODE: 0 - OFF

1 - ON

CS

MODE char
[0 - 1] *0

CS MODE
OK[CR][LF]
Ex: CS 0
OK[CR][LF]

11

Set TOTALIZER
start FLOW in
%F.S.

TS

CHANNEL
1 char. [1-4]

VALUE
float
[0-105.0]

TS CH VALUE
OK[CR][LF]
Ex: TS 2 5.0
OK[CR][LF]

12

Set TOTALIZER
stop VOLUME in
current volume
based E.U.

TP

CHANNEL
1 char. [1-4]

VOLUME
[0-999999.8]

TP CH VOLUME
OK[CR][LF]
Ex: TP 2 1000
OK[CR][LF]

13

Set TOTALIZER
MODE

TM

CHANNEL
1 char.
[1-4]

MODE [0-1]
0- DISABLE
1- ENABLE

ACTION
[0-2]
0 - NON
1- BUZER
2 - VALVE

CLOSE

TM CH MODE
ACTION OK[CR]
[LF]Ex: TM 1 1 2
OK[CR][LF]

14

Reset TOTALIZER
to ZERO

TZ

CHANNEL
1 char.
[1-4]

TZ CH OK[CR]
[LF]Ex: TZ 2
OK[CR][LF]

15

Read TOTALIZER
VOLUME
Returns volume in
current E.U.

TR

CHANNEL
1 char.
[1-4]

TOT#CH: VOL
EU[CR][LF]
TOT#2: 1005.5
L[CR][LF]

16

TOTALIZER Status
command Returns
current settings for
all available
channels (mode,
action, start flow)

SCT

NON

SCT M M A A SF
SF[CR][LF]
Ex: SCT 1 1 2 2
2.5 5.0[CR][LF]
(for two channels
SDPROC)

17

Second TOTALIZER
Status command.
Returns current
STOP VOLUME
settings for all
available channels.

STS

NON

STS VOL
VOL[CR][LF]
Ex: STS 1000.0
15000.0[CR][LF]
(for two channels
SDPROC)

18

Set ALARM MODE AM

CHANNEL
1 char. [1-4]

MODE [0-1]
0- DISABLE
1- ENABLE

ACTION
[0-2]
0 - NON
1- BUZER
2 - VALVE

CLOSE

DELAY
In seconds

[0 - 65535] AM
CH MODE
ACTION OK[CR]
[LF]Ex: AM 1 1
2 0 OK[CR][LF]

19

Set ALARM LOW
flow margin
in %F.S.

AL

CHANNEL
1 char.
[1-4]

VALUE
float
[0-105.0]

AL CH VALUE
OK[CR][LF] Ex: AL
2 5.0 OK[CR][LF]

GENERAL CONTROL COMMANDS

TOT

A

LIZER SETTINGS AND ST

A

T

US COMMANDS

ALARM SETTINGS AND

ST

A

T

US

COMMANDS

Advertising