Aalborg SDPROCs User Manual

Page 44

Advertising
background image

39

No Type

Description

Command Argument 1 Argument 2 Argument 3 Argument 4

Return string

2
0

Set ALARM HIGH
flow margin
in %F.S.

AH

CHANNEL
1 char.
[1-4]

VALUE
float
[0-105.0]

AH CH VALUE
OK[CR][LF]
Ex: AH 2 5.0
OK[CR][LF]

2
1

Read ALARM
STATUS Returns:
0 - NO ALARM
1 - HIGH ALARM
2 - LOW ALARM

AS

NON

AS ST ST[CR]
[LF] Ex: AS 0
2[CR][LF]
(example above
for two channels
SDPROC)

2
2

ALARM Status
command. Returns
current settings for
corresponding
channel
(mode, action, high
and low margins,
action delay)

SCA

CHANNEL
1 char.
[1-4]

A Ch1:
M A HM LM
D[CR][LF]
Ex: A Ch1: 1 2 2.5
5.0 0 [CR][LF]

2
3

RELAYS
ASSIGNMENT

RA

CHANNEL
1 char.
[1-4]

RELAY#
[0-1]
0 -Relay #1
1 -Relay #2

ACTION
[0-3]
0- No action
1- Alarm High
2- Alarm Low
3- Totalizer

RA CH RL#
ACTION
OK[CR][LF]
Ex: RA 2 0 3
OK[CR][LF]

2
4

Read RELAYS
ASSIGNMENT
STATUS Returns
current assignments
of the relays (two
for each channel)
for all available
channels.

SRS

NON

SRS A A A
A[CR][LF]
Ex: SRS 0 0
13[CR][LF]
(for two
channels
SDPROC)

2
5

Set BATCH
properties:
-mode [0-1]
-loop OFF/ON [0-1]
-number of the step

to execute [1-16].

BM

CHANNEL
1 char. [1-4]

MODE [0-1]
0- DISABLE
1- ENABLE

LOOP [0-1]
0- DISABLE
1- ENABLE

# STEPS
[1-16]

BM CH MD LP ST
OK[CR][LF]
Ex: BM 2 0 0 10
OK[CR][LF]

2
6

Set BATCH time
and set point values
for particular step
number [1-16].

BS

CHANNEL
1 char. [1-4]

STEP
NUMBER
[1-16]

SET POINT
float
[0-105.0]

TIME
In seconds
[0 - 99999]

BS CH ST SP TM
OK[CR][LF]
Ex: BS 1 1 100.0
60 OK[CR][LF]

2
7

Save BATCH array
to the SDPROC.

BW

NON

BW OK[CR][LF]

2
8

TIMER SETTINGS
Setup TIMER
PROGRAM Total
available up to 96 steps.
For each active step set
point and time string
has to be entered.
Time string has to be
16 characters long.

PS

CHANNEL
1 char. [1-4]

STEP
NUMBER
[0-96]

SET POINT
float
[0-105.0]

TIME
formatted
string:
[hh:mm,mm
/dd/yyyy]
Total 16 ch.

PS CH ST SP
TIME K[CR][LF]
Ex: PS 1 4 50.0
20:30,10/24/2002
OK[CR][LF]29
Save TIMER array
to the SDPROC.
PW NON PW
OK[CR][LF]

2
9

Save TIMER array
to the SDPROC.

PW

NON

PW OK [CR] [LF]

ALARM SETTINGS AND ST

A

T

US

COMMANDS

RELA

YS ASSIGNMENT AND ST

A

T

US

BA

TCH SETTINGS

TIMER SETTINGS

Advertising