Bard TCS22-***-003 User Manual

Page 10

Advertising
background image

2100-444-003A

Page 4

INPUTS

1 Indoor Temperature Sensor

Required

(Standard in TCS22)

2 Indoor Humidity Sensor

Optional

(Optional in TCS22)

3 -0 Unit #1 Blower Airflow Sensor

Required

(Standard in "V" Module)

-1 Unit #1 Compressor Lockout Relay

Required

(Standard in "V" Module)

-2 Unit #1 Dirty Filter Sensor

Optional

(Standard in "V" Module)

4 Unit #1 Discharge Air Sensor

Optional

(Standard in "V" Module)

5 Spare
6 Spare
7 Unit #1 Compressor Current Switch

Required

(Standard in "V" Module)

8 Spare
9 Fire Trouble

Optional

10 Fire Alarm

Optional

11 Spare
12

Door

Alarm Optional

13 Main Power Sensor

Optional

14 Occupied Override Switch

Required

(Standard in TCS22)

15 Outdoor Temperature Sensor

Required

(Standard in TCS22)

16 Outdoor Humidity Sensor

Required

(Standard in TCS22)

OUTPUTS

1 Spare
2 Cycle Power To Modem
3 Power Transfer Switch
4 Unit #1 Economizer (Y1)
5 Unit #1 Compressor (Y2)
6 Unit #1 Heater (W1)
7 Unit #1 Blower (G)
8 Spare
9 Spare
10 Spare
11 Spare
12 Shelter Alarm Circuit
13 Unit #1 is Lead Unit

14 Spare
15 Free Cooling
16 Power Failure