3 occupied heating setpoint, 4 unoccupied heating setpoint, 5 high temperature alarm setpoint – Bard TCS22-***-003 User Manual

Page 43: 6 low temperature alarm setpoint, 7 high humidity alarm setpoint, 8 low humidity alarm setpoint, 9 dehumidification setpoint, Occupied heating setpoint, Unoccupied heating setpoint, High temperature alarm setpoint

Advertising
background image

2100-444-003A

Page 37

5.3.4.3 OCCUPIED HEATING SETPOINT

The occupied heating setpoint requires an authority level of Supervisor or higher to change.

Anyone may view the setpoint value. The Occupied Heating Setpoint Range is from 68.0 to 70.0 F

o

. The

default value is 70.0 F

o

5.3.4.4 UNOCCUPIED HEATING SETPOINT

The unoccupied heating setpoint requires an authority level of Supervisor or higher to change. Anyone
may view the setpoint value. The Unoccupied Heating Setpoint Range is from 60.0 to 70.0 F

o

. The

default value is 68.0 F

o

5.3.4.5 HIGH TEMPERATURE ALARM SETPOINT

The high temperature alarm setpoint requires an authority level of Supervisor or higher to

change. Anyone may view the setpoint value. The High Temperature Alarm Setpoint Range is from 80.0
to 100.0 F

o

. The default value is 90.0 F

o

. The high alarm setpoint should always be set at least 7 degrees

higher then the unoccupied cooling setpoint. Nuisance alarms could occur if this requirement is not
followed.

5.3.4.6 LOW TEMPERATURE ALARM SETPOINT


The low temperature alarm setpoint requires an authority level of Supervisor or higher to change.

Anyone may view the setpoint value. The Low Temperature Alarm Setpoint Range is from 45.0 to 67.0
F

o

. The default value is 56.0 F

o

. The low alarm setpoint should always be set at least 4 degrees lower

then the unoccupied heating setpoint. Nuisance alarms could occur if this requirement is not followed.

5.3.4.7 HIGH HUMIDITY ALARM SETPOINT


The high humidity alarm setpoint requires an authority level of Supervisor or higher to change.

Anyone may view the setpoint value. The High Humidity Alarm Setpoint Range is from 55.0 to 85 %
RH. The default value is 60.0 % RH.

5.3.4.8 LOW HUMIDITY ALARM SETPOINT


The low humidity alarm setpoint requires an authority level of Supervisor or higher to change.

Anyone may view the setpoint value. The Low Humidity Alarm Setpoint Range is from 5.0 to 35 % RH.
The default value is 20.0 % RH.

5.3.4.9 DEHUMIDIFICATION SETPOINT


The dehumidification setpoint setpoint requires an authority level of Supervisor or higher to