6.4.4 ALARMS

TAB


The Alarms Tab will switch to the screen containing the Alarm information from the Controller.

The Alarm screen will allow the user to check the alarm status of the Zone Temperature, Zone Humidity,
Outdoor Temperature, Outdoor Humidity, Main Power, Door Alarm, Fire Alarm and Fire Trouble.
Blower, Compressor, and Filter alarms of the conditioning units can also be monitored.

Several alarms can be enabled or disabled by checking the alarm enable check box. Do not

disable an alarm that is in alarm. Doing so will lock the alarm on and it will not be able to be cleared or
acknowledged until the alarm is re-enabled.

All alarms can be acknowledged. Acknowledging an alarm resets the shelter alarm output to

normally open so that any new alarm will re-close the output and signify a new alarm. Most alarms are
self-clearing alarms. Once the condition that caused the alarm is corrected or goes away the alarm resets.

The compressor and blower alarms are not self clearing alarms and must be manually cleared

from the Override screen . These are the verify alarms.

An alarm can also be used to initiate a dial-out alarm call to a pager or printer. Clicking the Dial-

out enable check box enables dial-out alarms. The dial-out phone numbers are maintained under the Dial
Out tab.