1 #1 blower override, 1 blower override – Bard TCS22-***-003 User Manual

Page 46

Advertising
background image

2100-444-003A

Page 40

screen. Press the <F1> key. To override the displayed item press the <Change> key again. There are
seven (7) actions now available, On, Off, Reset, O/R On, O/R OFF, Clr Verify Alr, and Clear O/R. Use
the <Up> and <Down> keys to choose 1 of the 7 actions available. Not all actions are available for each
item. The available actions are shown above. Once the desired action is displayed press the <Enter> key
to initiate the action. If the action was accepted the screen will show the changed output or override
status.


If you do not have authority to override the outputs will not be highlighted. A supervisor

authority level is required override outputs. If you have authority to override the value will be
highlighted after pressing the <F1> key.


To enter a password, press <F2> key at any time. See the password section in this manual for

proper password entry method.











5.3.5.1 #1 BLOWER OVERRIDE


OVERRIDES
UNIT #1

F1 = EDIT MODE
ENTER TO EDIT
BLOWER OFF
OVR STATUS AUTO
VERIFY ALR STAT OK
ACTION NO OPER.

ECON OUTPUT OFF
OVR STATUS AUTO
ACTION NO OPER

COMP. OUTPUT OFF
OVR STATUS AUTO
VERIFY ALR STAT OK
ACTION NO OPER

HEAT OUTPUT OFF
OVR STATUS AUTO
ACTION NO OPER

LEAD UNIT IS 1
CHANGE LEAD UNIT ***

CONT. BLOWER OFF

Advertising