3.4.2 TCS22 STARTUP CHECKLIST

Apply power to
WallMount

air-

Conditioners

Apply power to WallMount

air-Conditioners. Wait two minutes for

wallmount time delays to expire.

Apply power to TCS22 Apply power to TCS22 and monitor LEDs on the front of the

controller. The controller performs a self test on startup. Upon
application of power, 9 LEDs will light.

System Power led will light and stay lit

Unit #1 is Lead Unit, Unit #2 is Lead Unit, Free Cooling, Power
Failure LEDs will light for 5 seconds and then resume normal
operation

System Rx and Tx and Local Rx and Tx will all flash on, flash off,
flash on and then flash off during this five seconds and will then
resume normal operation .

This completes the self test and controller will now start controlling
per the sequence of operation.

Connect to Controller

Use the DAK or Laptop PC to connect to controller to change
setpoints.

See Section 5.0 for DAK operation procedures.

See Section 6.0 for direct connect PC operation.