5 overrides unit #1 screen, Table 2. enthalpy lookup table – Bard TCS22-***-003 User Manual

Page 45

Advertising
background image

2100-444-003A

Page 39

Table 2. Enthalpy Lookup Table



Desired
Indoor
Temp.


Desired Indoor % Relative Humidity

Desired
Indoor

Temp.

35%

40%

45%

50%

55%

60%

65%

70%

85

23.00

25.00 27.25 29.50 31.50 33.50 35.75 37.75

84

22.50 24.50 26.75 29.00 30.75 32.75 35.00 36.75

83

22.00 24.00 26.25 28.25 30.25 32.00 34.25 36.00

82

21.50 23.50 25.25 27.50 29.50 31.50 33.25 35.00

81

20.75 22.00 24.50 26.75 29.00 30.75 32.50 34.25

80

20.25 22.25 24.25 26.25 28.25 30.00 31.75 33.25

79

20.00 21.50 23.75 25.50 27.50 29.25 30.00 32.50

78

19.50 21.00 23.00 25.00 27.00 28.50 30.25 31.75

77

19.00 20.50 22.50 24.50 26.25 28.00 29.75 31.00

76

18.50 20.25 22.00 24.00 25.50 27.25 29.00 30.25

75

18.00 19.50 21.50 23.25 25.00 26.50 28.25 29.50

5.3.5 Overrides Unit #1 Screen


Caution: Overrides remain in effect until they are either cleared by the operator or power is cut

to the controller. Use with caution.

Note: Outputs cannot be overridden until alarms have been cleared. This applies to blowers and

compressors.

The Overrides menu set displays the following information about the controller:

#1 Blower Override

O/R On, O/R Off, Clr Verify Alr, Clr O/R

#1 Economizer Override

O/R On, O/R Off, Clr Verify Alr, Clr O/R

#1 Compressor Override

O/R On, O/R Off, Clr Verify Alr, Clr O/R

#1 Heater Override

O/R On, O/R Off, Clr Verify Alr, Clr O/R

Continuous

Blower

On/Off

Change Lead Unit

***/CHG

From this menu you can display the current status of the item and, with the proper authorization,

override the item. The values displayed for each of these points is updated every ten (10) seconds.


Pressing the <Up> or <Down> key will scroll up or down respectively through the screen on

page 43 showing four lines at a time.


To override an output, scroll up or down until the output that is to be changed is visible on the