Sealing the endlaps – Mueller Pre-Fab User Manual

Page 65

Advertising
background image

www.muellerinc.com

E-19

sealInG THe enDlaPs

At the panel endlaps place a run of sealant tape across the full panel width ½" below the fastener
line . The panel endlaps have a 12" minimum overlap located over a purlin as shown . Locate the
fasteners 1” above the purlin web according to the fastener layout .

Sealant

Tape

Sealant

Tape

12" Lap

Ridge

Eave

Purlin

Roof Panel

Purlin Web

Roof Fastener

noTe: Do not step on panel endlaps until fully secure with fasteners.